Veritas NetBackup™ 5330 Appliance Product Description

Last Published:
Product(s): Appliances (5330 3.0)

Environmental specifications

The following table lists the requirements for the NetBackup 5330 Appliance and the storage shelves.

Table: Environmental specifications

Component

Requirement

Operating temperature

10°C to 35°C (50°F to 95°F)

Storage temperature

-40°C to 70°C (-40°F to 158°F)

Transportation temperature

-40°C to 70°C (-40°F to 158°F)

Temperature gradient

10°C/h

Operating humidity

10%RH to 85%RH

Operating altitude

-30 meters to 3,000 meters

In altitudes from -60 meters to +1,800 meters, the ambient temperature ranges from 5°C to 35°C. When the altitude ranges from 1,800 meters to 3,000 meters, the environment temperature decreases by 0.6°C when the altitude increases by 100 meters.

Storage altitude

-30 meters to 3,000 meters

Noise

< 72 A-weighted decibel

This value reflects the maximum noise of the appliance when the ambient temperature is 25°C.